Infrastructure project supply across Georgia · since 2019
Home/Products/Valves & Dismantling Joints/Resilient-seated gate valve
Resilient-seated gate valve
Flange, illustration
Line drawing
Gate valves installed on a blue pipeline in a trench
1 / 4
Overview

A wedge gate valve with a fully EPDM-encapsulated wedge that seals against a smooth bore, so nothing collects in the seat. For drinking-water and wastewater networks, buried service with an extension spindle and surface box, or chambers.

Key specifications

Nominal sizeDN 50–1000
Pressure ratingPN 10 / PN 16 / PN 25
Body & bonnetDuctile iron EN-GJS-400 (GGG40) / EN-GJS-500 (GGG50)
WedgeDuctile iron, fully EPDM-encapsulated
CoatingFusion-bonded epoxy, inside and out
ConnectionFlanged, drilling to EN 1092–2
Face-to-faceEN 558 series 14 (short) · series 15 on request
StandardsEN 1074–1, EN 1074–2, EN 1171
Nominal sizeDN 50–1000
Pressure ratingPN 10 / PN 16 / PN 25
Body & bonnetDuctile iron EN-GJS-400 (GGG40) / EN-GJS-500 (GGG50)
WedgeDuctile iron, fully EPDM-encapsulated
Variants

Choose sizes and add to your quoteVariants · PN 16

DNPNL, mmH, mmWeight, kgAvailabilityQtyAction
DN 501615026512Tbilisi
0
DN 801618031519Tbilisi
0
DN 1001619035024Tbilisi
0
DN 1501621044040Tbilisi
0
DN 2001623053062Batumi
0
DN 300162707151183–5 wks
0
DN 350–100010–25Per datasheetTo orderRequest sizing →
DN 50Tbilisi

L 150 · H 265 mm · 12 kg

0
DN 80Tbilisi

L 180 · H 315 mm · 19 kg

0
DN 100Tbilisi

L 190 · H 350 mm · 24 kg

0
DN 150Tbilisi

L 210 · H 440 mm · 40 kg

0
DN 200Batumi

L 230 · H 530 mm · 62 kg

0
DN 3003–5 wks

L 270 · H 715 mm · 118 kg

0
DN 350–1000To order

PN 10–25 · Per datasheet

Request sizing →

Dimensions are indicative for EN 558 series 14, PN 16. Confirm against the datasheet before ordering. Price on request.

Compatible products

Complete the valve assembly

Flange adapter for PE pipe

DN 50–400PN 16
Tbilisi

Surface box + extension spindle

Ductile ironB125
Tbilisi
FAQ

Gate valve questionsFAQ

Resilient-seated or metal-seated?

Resilient-seated is the standard for water networks: drop-tight shut-off and no seat pocket to trap debris. Metal-seated suits high-temperature or abrasive media.

Which PN for a gravity-fed village network?

PN 10 is usually enough for gravity-fed and low-pressure village networks. Choose PN 16 where the working pressure plus surge can pass 10 bar, and PN 25 for pumped mains. Send us the profile and we confirm.

Do you supply 3.1 inspection certificates?

Yes. EN 10204 3.1 certificates and the EN 1074 conformity certificate are supplied with delivery. Ask for them in your quote request.