Key facts
| Outside diameter, mm | Min. wall, mm | Mass, kg/m |
|---|---|---|
| 63 | 3.8 | 0.67 |
| 110 | 6.6 | 2.04 |
| 160 | 9.5 | 4.27 |
| 200 | 11.9 | 6.68 |
| 315 | 18.7 | 16.54 |
| 400 | 23.7 | 26.62 |
| 630 | 37.4 | 66.15 |
Where SDR 17 is used
- Water distribution networks at moderate pressure
- Village and district supply lines
- Irrigation mains where PN10 is enough
Wall thickness is the minimum per EN 12201-2 as commonly tabulated; mass is theoretical at 0.95 g/cm³.
How it compares
Against SDR 11 (PN16) the wall is thinner and the pipe cheaper per metre; against SDR 26 (PN6) it has more pressure margin. For most distribution networks it is the middle option.
Jointing
PE100 is joined by butt fusion or electrofusion fittings. GON supplies the fittings, valves and boxes with the pipe, so one order covers the line.
How to write it in the BOQ
“PE100 pressure pipe DN110 × 6.6 mm, SDR 17, PN10, EN 12201, for butt-fusion or electrofusion jointing.”